| 1 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Plant Area spit bins was found in pathatic condition, need to be removed. | A&S | | Closed | |
| 2 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Plant and Utilities area , catchment basins along with grating cleaning to be carried out. | Civil | | Closed | |
| 3 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Stagnant water was observed in new CW diesel engine pump foundation. | Civil | | Closed | |
| 4 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Around new CW diesel engine pump foundation, redundant material was found, need to be removed. | Stationary | | Closed | |
| 5 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | At Tk-44 yard, poor housekeeping was observed. | Operation | | Closed | |
| 6 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Wild bushes need to be removed from TK-44 yard and around utility transformer ( Near 2603-J/JA room). | Civil | | Closed | |
| 7 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Near 113-J concrete slab was found damaged. | Civil | | Closed | |
| 8 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | MP steam tie-in point near 101-E first platform above 125-J , clamped portion to be tightened against seepage. | Stationary | | Closed | |
| 9 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Around 201-C4 area housekeeping is required. | Operation | | Closed | |
| 10 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Plant area dust bins was damaged, need to be replaced. | A&S | | Closed | |
| 11 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | At Cooling water supply flowmeter, metallic plate handles to be fixed properly against tripping issue. | Stationary | | Closed | |
| 12 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Tagging of CW side stream pump ( 2302-J) was found missing. | Civil | | Closed | |
| 13 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Electrical Cables conduiting to be carried out around Cooling tower basin strainer ladder. | Electrical | | Closed | |
| 14 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Instrument Cables conduiting to be carried out around Cooling tower basin strainer ladder. | Instrument | | Closed | |
| 15 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Near 2401-L , Concrete pipe rack and supports were found in deteriorated condition. | Civil | | Closed | |
| 16 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Near LPG to MCOs iso-valves , lines supports were found in deteriorated condition. | Civil | | Closed | |
| 17 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Old softening unit drain lines was found rusty need to be replaced. | Stationary | | Closed | |
| 18 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | Near 2404-J drain channel to be cleaned. | Civil | | Closed | |
| 19 | 2025-10-24 | 2025-26 | Q1 | Korangi Refinery | Process & Utilities | Plant Area | At LPG to MCOs iso-valves pit , safety sign board to be renewed. | Operation | | Closed | |
| 20 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Tank # 4 | Sand bags and left over material were found near crude pump, condenser and tank # 4, need to be removed. | Civil | | Closed | |
| 21 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | 1101-JB/JO | Nuts of strainer flange of 1101-JB/JO pump was missing. | Stationary | | Closed | |
| 22 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | 1101-JB | Grass was grown on pneumatic valve of 1101-JB, need to be remo | Civil | | Closed | |
| 23 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | 1101-JB | Insulation was missing on 1101-JB discharge line. | Civil | | Closed | |
| 24 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | 1101-CA | Steam drain line's funnel of 1101-CA was found damaged and not properly aligned as well. | Stationary | | Closed | |
| 25 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Crude pump office | Near crude pump office, decanting board of lube oil drums was pitted and faded, need to repaint and repaired. | Stationary | | Closed | |
| 26 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | API separator | Hay basket, dry leaves and other left over materials need to be removed from API separator area. | Stationary | | Closed | |
| 27 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | API separator | Railing of API separator was found damaged, need to be repaired. | Stationary | | Closed | |
| 28 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | WWTP | Railing of new constructed pit for effluent line near WWTP was found missing. | Construction | | Closed | |
| 29 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Road # 14 | Sludge in rain drum and dry bushes was observed along road No. 14, need to be cleaned and area to be dressed up as well | Civil | | Closed | |
| 30 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Fire hydrant No. 100 and 96 | Leakage was observed from gland of isolation valve (15A) of FW, 4" valve of fire hydrant No. 100 and 96, need to rectified. | F&S | | Closed | |
| 31 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Tank # 32 | Safety sign board near gantry and tank # 32 needs to be renewed. | HSEQ | | Closed | |
| 32 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | HSD Gantry Pump | Metallic cover of cable trench of HSD gantry pump was found missing. | Stationary | | Closed | |
| 33 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Pump 2502-J | Oil traces was observed around MS pump and tagging of pump 2502-J was found missing. | Logistic | | Closed | |
| 34 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Loading arm at bay # 5. | Seepage was observed from the loading arm at bay # 5. | Logistic | | Closed | |
| 35 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Road # 1 | On road # 1, safety sign for speed limit needs to be renewed. | HSEQ | | Closed | |
| 36 | 2026-01-08 | 2025-26 | Q2 | Korangi Refinery | Tank Farm | Road # 1 | Safety sign showing direction on road # 1, needs to be renewed. | HSEQ | | Closed | |
| 37 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Lab | The UPS outside the AAS was installed on a wooden board should be inspected to verify proper earthing and bonding compliance. | Lab | | Open | |
| 38 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Lab | Tangled cables located behind the total nitrogen equipment should be properly organized to eliminate potential electrical hazards. | Lab | | Closed | |
| 39 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Lab | Risk assessment needs to be revised regarding prohibition of use of cell phones. | Lab | | Closed | |
| 40 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Lab | The outdated TBTs were pasted at the laboratory notice board need to be updat | Lab | | Closed | |
| 41 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Lab | The visibilty of some safety guidelines/operating instruction posters was not clear, it should remain clearly visible at all times. | Lab | | Open | |
| 42 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Electrical wire was found hanging from the warehouse roof. | Lab | | Closed | |
| 43 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | One Item was missing in the First Aid Box. | Warehouse | | Closed | |
| 44 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Electrical wire was found hanging from the warehouse roof. | Warehouse | | Closed | |
| 45 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Poor housekeeping conditions were observed near the warehouse rack area. | Warehouse | | Closed | |
| 46 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | A sack or material bag was found lying between racks, creating a tripping hazard. | Warehouse | | Closed | |
| 47 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Inspection tag was not available on the temporary scaffolding racks in G2. | Warehouse | | Closed | |
| 48 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | WD-40 cans were found in G-1 need to be relocated. | Warehouse | | Closed | |
| 49 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Unlabelled chemical drums or cans were found outside G2, and corresponding MSDS documents were missing. | Warehouse | | Closed | |
| 50 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Inspection and painting of roof angles outside of G-01 warehouse are required. | Warehouse | | Open | |
| 51 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | MSDS documents for BPR and other chemicals were not accessible. | Warehouse | | Closed | |
| 52 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Wheel stoppers were missing under the electrical cable drums. | Warehouse | | Closed | |
| 53 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | One tyre of foam trolley was found punctured. | Warehouse | | Closed | |
| 54 | 2026-06-03 | 2025-26 | Q3 | Korangi Refinery | Gate 1 to Gate 3 | Warehouse | Excess to fire hydrant 4A was found obstructed. | Warehouse | | Closed | |